IV. 8. WIRING DIAGRAMS
Dissemble the bolts from the cover. (If there isn't a cover
on the outdoor unit, disassemble the bolts from the
maintenance board, and pull it in the direction of the arrow
to remove the protection board.) (Refer to Fig. 8-1)
Protection board
Cover
Fig. 8-1
IV. 8.1 Network address set
Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner
in LAN is set by code switches S1 & S2 on the Main Control Board of the indoor unit, and the set range is 0 - 63.
Table 8-1
Toggle switch set
Network address code
S1 S2
00 ~ 15
16 ~ 31
32 ~ 47
48 ~ 63
IV. 8.2 Specification of power
Table 11-2
The power cord type designation is H07RN-F
IV. 8.3 Wiring diagrams
 For all models 18 – 24
Ground wiring
Ground wiring
Ground wiring
Power sup ply
Power sup ply
Switch/Fuse
(Available locally)
Switch/Fuse
(Available loca lly)
Po wer wiring ( in door)
Power linking wiring (Outdoor)
Weak elec-signal link wiring
Indo o r
Unit
Indo o r
Unit
Out door
Unit
Power sup ply
Ground the air conditioner properly in case
to affect its
anti-interference function
!
CAUTION
The wiring diagram of the air-conditioner are shown as follows. When wiring, please choose the corresponding
figure, or it may cause damage.
24 18 SLEDOM
INDOOR UNIT POWER
ESAHP-1 ESAHP
zH05 ,~V042-022 TLOV DNA YCNEUQERF
0.1 x 3 )²mm( GNIRIW REWOP
01/51 )A( ESUF/REKAERB TIUCRIC
OUTDOOR UNIT POWER
ESAHP-1 ESAHP
FREQUENCY AND VOLT 220-240V~, 50Hz
POWER WIRING (mm²) 3 x 2.5
CIRCUIT BREAKER/FUSE (A) 30/20
INDOOR/OUTDOOR CONNECTING WIRING (mm²) 2-core shielded wire 2x0.5